Stairs.  Entry group.  Materials.  Doors.  Locks.  Design

Stairs. Entry group. Materials. Doors. Locks. Design

» Typical requirements for premises for the placement of heat metering units for consumers. What is an individual heating point (IHP) Login to IHP

Typical requirements for premises for the placement of heat metering units for consumers. What is an individual heating point (IHP) Login to IHP

Below are the requirements of regulatory documents relating to the premises of a heating point. The above list of requirements is not exhaustive and will expand over time. The technical requirements for the Heat Substation Premises were taken from the regulatory documentation governing the design, installation and operation of engineering systems of residential and public buildings and may differ from similar rules for objects for other purposes.

DBN V.2.5-39 Heat networks

Clause 16.5 - Chapter 16 Heating points

Equipment for sanitary systems of buildings and structures may be located in the premises of heating points.

In heating points built into residential buildings, pumps with an acceptable (low) noise level should be installed only.

Clause 16.20 - Chapter 16 Heating points

A drain should be installed in the floor of the heating unit, and if it is impossible to drain water by gravity, a drainage pit should be equipped with a size of at least 0.5 x 0.5 x 0.8 m. The pit should be covered with a removable grate.

It is allowed to drain water not into a sump or drain of a heating point, but into special containers.

A single sump pump should be used to pump water from the catch basin to the sewer system, drainage system or associated drainage system.

A pump designed to pump water from a catchment pit is not allowed to be used for flushing a heat consumption system.

SNiP 2.04.01 Internal water supply and sewerage of buildings

Clause 12.3 - Chapter 12 Pumping units

Pumping units supplying water for domestic drinking, fire-fighting and circulation needs should, as a rule, be located in the premises of heating points, boiler rooms and boiler rooms.

Clause 12.4 - Chapter 12 Pumping units

It is not allowed to locate pumping units (except for fire departments) directly under residential apartments, children's or group rooms of kindergartens and nurseries, classrooms of secondary schools, hospital premises, workrooms of administrative buildings, auditoriums of educational institutions and other similar premises.

Pumping units with fire-fighting pumps and hydropneumatic tanks for internal fire extinguishing are allowed to be located in the first and basement floors of buildings of I and II degrees of fire resistance made of non-combustible materials. In this case, the premises of pumping units and hydropneumatic tanks must be heated, fenced off with fire walls (partitions) and ceilings and have a separate exit to the outside or to the staircase.

Notes:

  • 1. In some cases, in agreement with local sanitary and epidemiological service authorities, it is allowed to locate pumping units next to the listed premises, while the total noise level in the premises should not exceed 30 dB.
  • 2. Rooms with hydropneumatic tanks should be located directly (next to, above, below) with rooms where a large number of people can stay simultaneously - 50 people. and more (auditorium, stage, dressing room, etc.) are not allowed. Hydropneumatic tanks may be located on technical floors. When designing hydropneumatic tanks, the requirements of the “Rules for the Design and Safe Operation of Pressure Vessels” of the USSR State Mining and Technical Supervision Authority should be taken into account. In this case, the need to register hydropneumatic tanks is established by paragraphs 6-2-1 and 6-2-2 of these Rules.
  • 3. It is not allowed to locate fire pumping installations in buildings in which the power supply is interrupted during the absence of maintenance personnel.

SNiP 2.04.05 Heating, ventilation and air conditioning

Clause 10.8 - Chapter 10 Space planning and design solutions

With centralized heat supply to buildings, they must provide premises for individual heating points, which must meet the requirements of the standards for the design of heating networks. To place electronic devices for commercial heat consumption metering, it is necessary to provide premises protected from unauthorized access that meet the requirements for the operation of these devices.

BTP - Block heating point - 1var. - this is a compact thermal-mechanical installation of complete factory readiness, located (placed) in a block container, which is an all-metal supporting frame with fencing made of sandwich panels.

IHP in a block container is used to connect heating, ventilation, hot water supply and technological heat-using installations of an entire building or part of it.

BTP - Block heating point - 2var. It is manufactured in a factory and supplied for installation in the form of ready-made blocks. May consist of one or more blocks. The block equipment is mounted very compactly, usually on one frame. Typically used when it is necessary to save space, in cramped conditions. Based on the nature and number of connected consumers, the BTP can be classified as either an ITP or a central heating substation. Supply of ITP equipment according to specifications - heat exchangers, pumps, automation, shut-off and control valves, pipelines, etc. - supplied in separate items.

BTP is a fully factory-ready product, which makes it possible to connect reconstructed or newly constructed facilities to heating networks in the shortest possible time. The compactness of the BTP helps to minimize the equipment placement area. An individual approach to the design and installation of block individual heating units allows us to take into account all the client’s wishes and translate them into the finished product. guarantee for the BTP and all equipment from one manufacturer, one service partner for the entire BTP. ease of installation of the BTP at the installation site. Manufacturing and testing of BTP in the factory - quality. It is also worth noting that for mass, block-by-block development or extensive reconstruction of heating points, the use of BTP is preferable compared to ITP. Since in this case it is necessary to install a significant number of heating points in a short period of time. Such large-scale projects can be implemented in the shortest possible time using only standard factory-ready BTP.

ITP (assembly) - the ability to install a heating unit in cramped conditions; there is no need to transport the assembled heating unit. Transport of individual components only. The delivery time of equipment is significantly shorter than that of BTP. The cost is lower. - BTP - the need to transport the BTP to the installation site (transportation costs), the dimensions of the openings for carrying the BTP impose restrictions on the overall dimensions of the BTP. Delivery time from 4 weeks. Price.

ITP - a guarantee for various components of a heating unit from different manufacturers; several different service partners for various equipment included in the heating unit; higher cost of installation work, installation time, etc. That is, when installing ITP, the individual characteristics of a particular room and the “creative” solutions of a particular contractor are taken into account, which, on the one hand, simplifies the organization of the process, and on the other, can reduce the quality. After all, it is much more difficult to perform a weld seam, a pipeline bend, etc. “in place” with high quality than in a factory environment.

SNiP 41-02-2003

14.1 Heating points are divided into:
individual heating points (ITP)— for connecting heating, ventilation, hot water supply and technological heat-using installations of one building or part of it;
central heating points (CHS)- the same, two buildings or more.
14.2 Thermal points provide for the placement of equipment, fittings, monitoring, control and automation devices, through which the following is carried out:
transformation of the type of coolant or its parameters; control of coolant parameters;
accounting for heat loads, coolant and condensate flow rates;
regulation of coolant flow and distribution across heat consumption systems (through distribution networks in central heating stations or directly to heating and heating systems);
protection of local systems from emergency increases in coolant parameters;
filling and replenishing heat consumption systems;
collection, cooling, return of condensate and quality control;
heat accumulation;
water treatment for hot water supply systems.
At a heating point, depending on its purpose and local conditions, all of the listed activities or only part of them can be carried out. Devices for monitoring coolant parameters and metering heat consumption should be provided at all heating points.
14.3 The installation of an ITP input is mandatory for each building, regardless of the presence of a central heating point, while the ITP provides only for those measures that are necessary for connecting a given building and are not provided for in the central heating point.
14.4 In closed and open heat supply systems, the need to install central heating stations for residential and public buildings must be justified by technical and economic calculations.
14.5 In the premises of heating points it is allowed to place equipment for sanitary systems of buildings and structures, including booster pumping units that supply water for domestic drinking and fire-fighting needs.
14.6 Basic requirements for the placement of pipelines, equipment and fittings in heating points should be taken according to Appendix B.
14.7 The connection of heat consumers to heating networks at heating points should be provided according to schemes that ensure minimum water consumption in heating networks, as well as heat savings through the use of heat flow regulators and limiters of the maximum flow of network water, correction pumps or elevators with automatic control that reduce the temperature water entering heating, ventilation and air conditioning systems.
14.8 The design temperature of water in the supply pipelines after the central heating point should be accepted:
when connecting heating systems of buildings according to a dependent scheme - equal, as a rule, to the calculated water temperature in the supply pipeline of the heating networks to the central heating point;
with an independent circuit - no more than 30 °C below the design temperature of water in the supply pipeline of the heating networks to the central heating point, but not higher than 150 °C and not lower than the design temperature accepted in the consumer’s system.
Independent pipelines from central heating stations for connecting ventilation systems with an independent connection scheme for heating systems are provided at a maximum thermal load for ventilation of more than 50% of the maximum thermal load for heating.
14.9 When calculating the heating surface of water-water heaters for hot water supply and heating systems, the water temperature in the supply pipeline of the heating network should be taken equal to the temperature at the break point of the water temperature graph or the minimum water temperature, if there is no break in the temperature graph, and for heating systems - also the temperature water corresponding to the calculated outside air temperature for heating design. The larger of the obtained values ​​of the heating surface should be taken as the calculated value.
14.10 When calculating the heating surface of hot water supply water heaters, the temperature of the heated water at the outlet from the water heater into the hot water supply system should be taken to be at least 60 °C.
14.11 For high-speed sectional water-to-water water heaters, a countercurrent flow pattern of coolant should be adopted, while heating water from the heating network should flow:
in water heaters of heating systems - in tubes;
the same for hot water supply - into the interpipe space.
In steam-water water heaters, steam must enter the inter-tube space.
For hot water supply systems with steam heating networks, it is allowed to use capacious water heaters, using them as hot water storage tanks, provided that their capacity corresponds to that required in the calculation for storage tanks.
In addition to high-speed water heaters, it is possible to use other types of water heaters that have high thermal and operational characteristics and small dimensions.
14.12 The minimum number of water-to-water heaters should be:
two, connected in parallel, each of which must be calculated for 100% of the heat load - for heating systems of buildings that do not allow interruptions in the heat supply;
two, each designed for 75% of the heat load, for heating systems of buildings constructed in areas with a design outdoor temperature below minus 40 °C;
one for other heating systems;
two, connected in parallel in each heating stage, designed for 50% of the heat load each - for hot water supply systems.
With a maximum heat load for hot water supply of up to 2 MW, it is allowed to provide one hot water supply heater in each heating stage, except for buildings that do not allow interruptions in the supply of heat to hot water supply.
When installing steam-water water heaters in heating, ventilation or hot water supply systems, their number must be at least two, connected in parallel; backup water heaters need not be provided.
For technological installations that do not allow interruptions in the heat supply, backup water heaters must be provided, designed for the heat load in accordance with the operating mode of the enterprise's technological installations.
14.13 Pipelines should be equipped with fittings with shut-off valves with a nominal bore of 15 mm for releasing air at the highest points of all pipelines and with a nominal bore of at least 25 mm for draining water at the lowest points of water and condensate pipelines.
It is permissible to install devices for draining water not in the central heating station pit, but outside the central heating station in special chambers.
14.14 Mud traps should be installed:
at the heating point on the supply pipelines at the inlet;
on the return pipeline in front of control devices and water and heat flow metering devices - no more than one;
in ITP - regardless of their availability in the central heating center;
in thermal units of consumers of the 3rd category - on the supply pipeline at the inlet.
Filters should be installed in front of mechanical water meters (vane, turbine), plate heat exchangers and other equipment along the water flow (as required by the manufacturer).
14.15 At heating points, it is not allowed to install starting jumpers between the supply and return pipelines of heating networks, as well as bypass pipelines in addition to pumps (except for booster pumps), elevators, control valves, mud traps and devices for metering water and heat consumption.
Overflow regulators and steam traps must have bypass piping.
14.16 To protect pipelines and equipment of centralized hot water supply systems connected to heating networks through water heaters from internal corrosion and scale formation, water treatment should be provided, usually carried out in a central heating station. In ITP, only magnetic and silicate water treatment is allowed.
14.17 Treatment of drinking water should not worsen its sanitary and hygienic indicators. Reagents and materials used for water treatment that have direct contact with water entering the hot water supply system must be approved by the State Sanitary and Epidemiological Supervision authorities of Russia for use in domestic drinking water supply practice.
14.18 When installing storage tanks for hot water supply systems in heating points with vacuum deaeration, it is necessary to protect the inner surface of the tanks from corrosion and the water in them from aeration by using sealing liquids. In the absence of vacuum deaeration, the internal surface of the tanks must be protected from corrosion through the use of protective coatings or cathodic protection. The design of the tank should include a device that prevents sealing liquid from entering the hot water supply system.
14.19 For heating points, supply and exhaust ventilation should be provided, designed for air exchange determined by heat release from pipelines and equipment. The calculated air temperature in the work area in the cold period of the year should be taken no higher than 28 °C, in the warm period of the year - 5 °C higher than the outside air temperature according to parameters A. When placing heating points in residential and public buildings, a verification calculation of heat inputs from heating point into adjacent rooms. If the permissible air temperature in these rooms exceeds the permissible air temperature, measures should be taken for additional thermal insulation of the enclosing structures of adjacent rooms.
14.20 A drain should be installed in the floor of the heating unit, and if gravity drainage of water is not possible, a drainage pit should be installed measuring at least 0.5 ‘0.5 x 0.8 m. The pit is covered with a removable grate.
To pump water from the catchment pit into the sewerage system, drainage system or associated drainage, one drainage pump should be provided. A pump designed for pumping water from a catchment pit is not allowed to be used for flushing heat consumption systems.
14.21 At heating points, measures should be taken to prevent noise levels from exceeding those allowed for premises in residential and public buildings. Heating units equipped with pumps are not allowed to be placed adjacent to or above the premises of residential apartments, dormitories and playrooms of preschool institutions, sleeping quarters of boarding schools, hotels, hostels, sanatoriums, rest homes, boarding houses, wards and operating rooms of hospitals, premises with long stays patients, doctors' offices, auditoriums of entertainment enterprises.
14.22 The minimum clear distances from free-standing ground central heating centers to the external walls of the listed premises must be at least 25 m.
In particularly cramped conditions, it is permissible to reduce the distance to 15 m, provided that additional measures are taken to reduce noise to a level acceptable according to sanitary standards.
14.23 Based on their placement on the general plan, heating points are divided into free-standing, attached to buildings and structures, and built into buildings and structures.
14.24 Heating units built into buildings should be located in separate rooms near the outer walls of buildings.
14.25 The following exits must be provided from the heating point:
if the length of the heating point room is 12 m or less - one exit to the adjacent room, corridor or staircase;
if the length of the heating point room is more than 12 m, there are two exits, one of which should be directly outside, the second to the adjacent room, staircase or corridor.
The premises of heating points for consumers of steam with a pressure of more than 0.07 MPa must have at least two exits, regardless of the dimensions of the room.
14.26 There is no need to provide openings for natural lighting of heating points. Doors and gates must open from the room or building of the heating point away from you.
14.27 In terms of explosion and fire hazards, the premises of heating points must comply with category D according to NPB 105.
14.28 Heating units located in industrial and warehouse buildings, as well as administrative buildings of industrial enterprises, residential and public buildings, must be separated from other premises by partitions or fences that prevent unauthorized persons from accessing the heating unit.
14.29 For installation of equipment whose dimensions exceed the dimensions of the doors, installation openings or gates in the walls should be provided in ground-based heating units.
In this case, the dimensions of the installation opening and gate should be 0.2 m larger than the overall dimensions of the largest equipment or pipeline block.
14.30 To move equipment and fittings or integral parts of equipment units, inventory lifting and transport devices should be provided.
If it is impossible to use inventory devices, it is allowed to provide stationary lifting and transport devices:
with a mass of transported cargo from 0.1 to 1.0 tons - monorails with manual hoists and crampons or single-girder manual overhead cranes;
the same, more than 1.0 to 2.0 t - single-girder manual overhead cranes;
the same, more than 2.0 t - single-girder electric overhead cranes.
It is allowed to provide for the possibility of using mobile lifting and transport equipment.
14.31 To service equipment and fittings located at a height of 1.5 to 2.5 m from the floor, mobile platforms or portable devices (stepladders) must be provided. If it is impossible to create passages for mobile platforms, as well as to maintain equipment and fittings located at a height of 2.5 m or more, it is necessary to provide stationary platforms with fencing and permanent stairs. The dimensions of platforms, stairs and fences should be taken in accordance with the requirements of GOST 23120.
The distance from the level of the stationary platform to the upper ceiling must be at least 2 m.
14.32 In central heating stations with permanent staff, a bathroom with a washbasin should be provided.

8.1 Automated individual heating points (IHP), equipped at the inputs of heating networks into the building, should be provided for buildings with a calculated heat consumption for the heating period of 1000 GJ or more with the possibility of regulating the supply of heat for heating in individual technological zones and facades characterized by the same type influence of external (sun, wind) and internal (heat generation) factors. Heat supply for heating, ventilation and hot water systems should be provided through separate pipelines from the heating point.

8.2 ITP built into the buildings they serve should be designed taking into account SP 124.13330*. It is allowed to combine ITP with premises of ventilation and air conditioning units. ITP should be placed near the outer wall with the exit from the room directly outside or to the exit outside along the corridor no further than 12 m.

_________________

The height of the ITS premises should be less than 2.2 m from the floor to the bottom of the protruding structures. Building engineering systems must have automatic or manual air temperature control.

With a centralized supply of cold and hot water, electricity, gas and heat, and if there are several groups of premises in the building belonging to different organizations or owners, each group of premises must be equipped with autonomous metering devices for energy and water consumption.

Heat supply to a building or individual groups of premises can be carried out from centralized, autonomous or individual heat sources in accordance with SP 60.13330 and SP 89.13330.* In this case, gas fuel heat generators located in buildings must have closed furnaces (burners) and adjustable gas burners.

_________________

* Currently, there is no information in official sources about the adoption of this document mentioned hereinafter in the text. - Database manufacturer's note.

8.3 Separate branches of water heating systems with disconnecting devices outside these rooms are provided for the following rooms:

- conference hall;

- dining halls of canteens with production premises attached to them (for conference rooms with a number of seats up to 400 and dining halls of canteens with a number of seats up to 160, when they are located in the total volume of the building, separate branches may not be provided);

- auditorium, including stage;

- stage (universal stage);

- vestibule, foyer, corridors;

- dance hall;

- small halls in theaters and clubs, including the stage;

- libraries with a collection of 200 thousand items or more (for reading rooms, lecture halls and storage facilities);

- retail trade enterprises (for unloading premises and sales areas with an area of ​​400 m² or more);

residential premises in public buildings.

8.4 Heated floors should be provided on the ground floor of group preschools of all types, as well as in sleeping and changing rooms in preschools, medical and social organizations for children with musculoskeletal disorders. The average room temperature should be maintained within 23 °C.

8.5 It is recommended to use radiators as heating devices for heating stages in theaters and clubs. In this case, heating devices should be placed no higher than 0.5 m above the level of the stage plank on the back wall of the stage or rear stage.

8.6 Air removal from school classrooms should be provided through recreational rooms and sanitary facilities, as well as through exfiltration through external glazing, taking into account the requirements of SP 60.13330. When supply ventilation is mechanically driven or decentralized inflow in classrooms, natural exhaust ventilation should be provided at the rate of one or more air exchanges per hour.

For air heating, exhaust ducts from classrooms are not provided.

8.7 For air heating in school buildings, combined with ventilation, automatic control of the systems should be provided, including maintaining the design temperature and relative humidity in the premises during working hours within 40-60%, as well as ensuring the air temperature is not lower than during non-school hours 15 °C.

8.8 In schools with up to 200 students, ventilation without organized mechanical inflow is allowed.

8.9 Supply and exhaust ventilation systems should be provided separately for the premises of the auditorium and club complexes, stage (stage) service premises, as well as administrative and utility rooms, workshops and warehouses.

In cinemas with continuous film screenings, general leisure clubs and clubs with a total capacity of up to 375 people, this separation of systems may not be provided.

8.10 In repositories of rare books and manuscripts, as well as in library repositories with a collection volume of 1 million items or more, and in group I archive repositories, air conditioning should be provided.

8.11 In storage of valuable documents and depositories, according to the requirements of storage conditions, class 3 air conditioning should be provided.

8.12 In reading rooms, lecture halls and storage rooms of scientific libraries with a collection of 200 thousand storage units or more, it is allowed to use air heating combined with forced ventilation or an air conditioning system.

8.13 In storage rooms and archives with a capacity of more than 300 thousand storage units, as a rule, air heating combined with forced ventilation or an air conditioning system should be used. In other rooms of archive buildings, water heating should be provided.

8.14 For storage rooms, reading and lecture halls in library buildings with a collection of 200 thousand storage units or more, separate supply ventilation systems should be provided.

8.15 In public libraries with a collection of up to 50 thousand items of storage, when placing an area of ​​reading places together with an area of ​​book collections and reader services in one room and in archives with a capacity of up to 300 thousand items of storage, natural ventilation is allowed at the rate of at least one air exchange.

8.16 For lecture halls, reading rooms and library storage rooms, exhaust ventilation with natural impulse is allowed.

8.17 It is allowed to provide a single supply ventilation system to all premises, with the exception of conference rooms, premises of public catering establishments, cinema equipment and battery rooms, for each of which it is necessary to provide independent supply ventilation systems.

8.18 For rooms not equipped with a mechanical supply ventilation system, opening adjustable vents or air valves should be provided to supply outside air, located at a height of at least 2 m from the floor.

8.19 Independent exhaust ventilation systems should be provided for the following premises:

- bathrooms and smoking rooms;

- premises of catering establishments;

- premises for production, technical purposes and storage;

- laboratories, including training and other premises in accordance with the requirements of SP 60.13330.

8.20 It is recommended to provide exhaust ventilation from the bedrooms of sanatoriums and recreational facilities with a natural impulse.

In the living rooms of recreational facilities for the climatic region, it is recommended to provide exhaust ventilation with mechanical impulse.

8.21 Air removal from living rooms and rooms with bathrooms should be provided through the bathrooms with the installation of transfer grilles at the bottom of the bathrooms.

8.22 In storages of valuable documents and depositories, according to the requirements of storage conditions, class 3 air conditioning should be provided.

8.23 Exhaust ventilation with natural impulse may be provided in the premises of buildings with an estimated number of less than 300 people and a height of 1-3 floors.

8.24 To ensure regulatory requirements regarding permissible water pressures at sanitary fixtures, rational use of water and energy resources, it is necessary to provide:

pumping units with adjustable drive (engine speed);

single-zone water supply scheme with installation of floor pressure regulators.

8.25 The hydrostatic pressure in the drinking and fire-fighting water supply system at the level of the lowest located sanitary fixture should be no more than 4 atm. In the fire-fighting water supply system, during fire extinguishing, it is allowed to increase the pressure to no more than 6 atm at the level of the lowest located sanitary fixture.

8.26 The hydrostatic pressure at the level of the lowest fire hydrant in a separate fire-fighting water supply system, as well as in schemes where fire risers are used to supply transit utility and drinking water flows to the upper floor (in schemes with overhead distribution), should not exceed 9 atm in fire extinguishing mode.

8.27 Requirements for the internal fire water supply of buildings of cultural and entertainment institutions, libraries, archives and sports facilities are given in.

8.28 The installation of grease traps at industrial wastewater outlets should be provided for the following public catering establishments:

working on semi-finished products - with the number of seats in the halls being 500 or more;

working on raw materials - with the number of seats in the halls being 200 or more.

Food service units of preschool and general education institutions are equipped with grease traps according to design specifications.

8.29 In public buildings, a system for cleaning and dust collection, temporary (within sanitary standards) storage of garbage and the possibility of its removal should be provided.

In public buildings and complexes, the design of pneumatic waste disposal systems should be determined by the design assignment based on the technical and economic feasibility of their operation.

The means for removing waste from a building must be consistent with the cleaning system adopted in the locality where the building is located.

8.30 Garbage chutes (in the absence of a pneumatic garbage disposal system) should be provided in buildings:

3-story and higher buildings of higher educational institutions, hotels and motels with 100 beds or more;

5-story and higher buildings for other purposes.

Measures for organizing and installing garbage chutes are given in ( SP 31-108-2002 Garbage chutes for residential and public buildings and structures).

The need to install garbage chutes in other public buildings is established by the design assignment.

When adding an attic floor to an existing building, the existing waste disposal system may not be changed.

Access to a garbage collection vehicle must be provided to the doors of the building's garbage chamber. If it is impossible to organize access directly to the waste collection chamber, it is necessary to provide a place (platform) for placing waste collection containers.

For buildings that are not equipped with garbage chutes, a garbage collection chamber or utility area (necessarily with a hard surface) should be provided for separate waste collection.

8.31 A centralized or combined vacuum dust collection system should be provided in buildings:

- theaters, concert halls, museums;

- reading and lecture halls, library book depositories for 200 thousand items or more;

- stores with a sales area of ​​6,500 m² or more;

- hotels, sanatoriums, recreation and tourism institutions, inpatient medical institutions for 500 beds or more;

- in specialized buildings with increased sanitary and hygienic requirements (according to design instructions for medical institutions).

The need for a central or combined vacuum dust collection system in other buildings should be established by design assignment.

8.32 For a combined vacuum dust collection system, the service radius of one intake valve should be no more than 50 m.

8.33 In the absence of centralized or combined dust collection, the design of the vacuum cleaner filter cleaning chamber is determined according to the design specifications.

8.34 Structural solutions of building elements (including the location of voids, methods of sealing places where pipelines pass through structures, ventilation openings, placement of thermal insulation, etc.) must provide protection against the penetration of rodents.

9 Durability and maintainability

9.1 The building design must take into account the preservation of the strength and stability of load-bearing structures for the period established in the design assignment, subject to systematic maintenance, compliance with the rules of operation and repair of the building.

9.2 Structures, parts and finishing materials must be made of materials that are resistant to possible exposure to moisture, low and high temperatures, aggressive environments and other adverse factors, or protected in accordance with SP 28.13330.

9.3 It is necessary to provide measures to protect the building from the penetration of rain, melt, and groundwater into the thickness of the load-bearing and enclosing structures of the building, as well as the formation of condensation moisture in the external enclosing structures or for the ventilation of enclosed spaces or air spaces. In accordance with the requirements of regulatory documents, the necessary protective compounds and coatings must be used.

9 .4 Butt joints of prefabricated elements and multilayer structures must be designed to withstand thermal deformations and forces arising from uneven settlement of foundations and other operational influences. Sealing and sealing materials used in joints must retain elastic and adhesive properties when exposed to negative temperatures and wetness and be resistant to ultraviolet rays. Sealing materials must be compatible with the materials of protective and protective-decorative coatings of structures in places where they meet.

9.5 It must be possible to access the equipment, fittings and devices of the building’s engineering systems and their connections, as well as the load-bearing elements of the building’s covering for inspection, maintenance, repair and replacement.

According to SP 41-101-95

  • 2.8 Individual heating points must be built into the buildings they serve and located in separate rooms on the ground floor near the outer walls of the building. It is allowed to place ITP in technical undergrounds or in the basements of buildings and structures.
  • 2.9 Central heating points (CHS) should, as a rule, be provided separately. It is recommended to block them with other production premises.
    It is allowed to provide central heating stations attached to buildings or built into public, administrative or industrial buildings and structures.
  • 2.10 When placing heating units equipped with pumps inside residential, public, administrative and domestic buildings, as well as in industrial buildings, which are subject to increased requirements for permissible noise and vibration levels in premises and workplaces, the requirements of Section. 10.
  • 2.11 The buildings of detached and attached heating points must be one-story; it is allowed to construct basements in them for placing equipment, collecting, cooling and pumping condensate and constructing a sewage system.
      Separately standing heating points may be provided underground, provided:
    • lack of groundwater in the construction area and sealing of utility lines entering the heating station building, eliminating the possibility of flooding the heating station with sewerage, flood and other waters;
    • ensuring gravity drainage of water from the pipelines of the heating point;
    • ensuring automated operation of the heating point equipment without permanent maintenance personnel with an alarm system and partial remote control from the control center.
  • 2.12 In terms of explosion and fire hazards, the premises of heating points should be classified as category D.
  • 2.13 Heating units may be located in industrial premises of categories G and D, as well as in technical basements and underground areas of residential and public buildings. In this case, the premises of heating points must be separated from these premises by fences (partitions) that prevent unauthorized persons from accessing the heating point.
  • 2.14 When developing space-planning and design solutions for detached and attached buildings of heating stations intended for industrial and agricultural enterprises, it is recommended to provide for the possibility of their subsequent expansion.
  • 2.15 Heating points built into buildings should be located near the external walls of buildings at a distance of no more than 12 m from the exit from these buildings.
  • 2.16 The following exits must be provided from heating points built into buildings:
    • if the length of the heating point room is 12 m or less and it is located at a distance of less than 12 m from the exit from the building to the outside - one exit to the outside through a corridor or staircase;
    • if the length of the heating point room is 12 m or less and it is located at a distance of more than 12 m from the exit of the building - one independent exit to the outside;
    • if the length of the heating point room is more than 12 m, there are two exits, one of which must be directly outside, the second through a corridor or staircase.
    • The premises of heating points with coolant steam at a pressure of more than 1.0 MPa must have at least two exits, regardless of the size of the room.
  • 2.17 In underground free-standing or attached heating units, it is allowed to provide a second exit through an attached shaft with a hatch or through a hatch in the ceiling, and in heating units located in technical undergrounds or basements of buildings - through a hatch in the wall.
  • 2.18 Doors and gates from the heating point must open from the premises or building of the heating point away from you.
  • 2.19 It is recommended to use the equipment of heating points in a block design, for which it is necessary:
    • accept water heaters, pumps and other equipment in factory-ready units;
    • accept enlarged pipeline assembly blocks;
    • consolidate technologically interconnected equipment into transportable blocks with pipelines, fittings, instrumentation, electrical equipment and thermal insulation.
  • 2.20 The minimum clear distances from building structures to pipelines, equipment, fittings, between the surfaces of thermal insulation structures of adjacent pipelines, as well as the width of passages between building structures and equipment (in the clear) should be taken according to approx. 1.
  • 2.21 It is recommended to take the height of the premises from the finished floor mark to the bottom of the protruding ceiling structures (in the clear) at least, m:
    • for ground-based central heating stations - 4.2;
    • for underground - 3.6;
    • for ITP - 2.2.
    ITP design
    Requirements for heating points according to SP 41-101-95

    When placing ITP in basements and basements, as well as in technical underground areas of buildings, it is allowed to take the height of the premises and free passages to them at least 1.8 m.

  • 2.22 An installation (repair) site should be provided at the central heating point.
    The dimensions of the installation site in plan should be determined by the dimensions of the largest piece of equipment (except for tanks with a capacity of more than 3 m3) or a block of equipment and pipelines supplied assembled for installation, with a passage around it of at least 0.7 m.
    To carry out minor repairs of equipment, instruments and fittings, a place should be provided for installing a workbench.
  • 2.23 Condensate tanks and storage tanks with a capacity of more than 3 m3 should be installed outside the premises of heating points in open areas. In this case, provision must be made for thermal insulation of the tanks, installation of water seals built directly into the tank, as well as installation of fences with a height of at least 1.6 m at a distance of no more than 1.5 m from the surface of the tanks, preventing unauthorized persons from accessing the tanks.
  • 2.24 For installation of equipment whose dimensions exceed the dimensions of the doors, installation openings or gates in the walls should be provided in ground-based heating units. In this case, the dimensions of the installation opening and gate must be 0.2 m larger than the dimensions of the largest equipment or pipeline block.
  • 2.25 It is not necessary to provide openings for natural lighting of heating points.
  • 2.26 To move equipment and fittings or integral parts of equipment units, inventory lifting and transport devices should be provided.
      Stationary lifting and transport devices should be provided with:
    • with a mass of transported cargo from 150 kg to 1 t - monorails with manual hoists and crampons or single-girder manual overhead cranes;
    • the same, more than 1 to 2 tons - single-girder manual overhead cranes;
    • the same, more than 2 tons - single-girder electric overhead cranes.

    It is allowed to provide for the possibility of using mobile small-sized lifting and transport vehicles, provided that the entry and movement of vehicles through the heating point is ensured.
    Mechanization means can be specified by the design organization when developing a project for specific conditions.

  • 2.27 For water drainage, floors should be designed with a slope of 0.01 towards the drain or drainage pit. The minimum dimensions of the drainage pit should, as a rule, be at least 0.5 x 0.5 m in plan with a depth of at least 0.8 m. The pit should be covered with a removable grate.
  • 2.28 In the premises of heating points, it is necessary to provide for the finishing of fences with durable, moisture-resistant materials that allow easy cleaning, and it is necessary to do the following:
    • plastering the ground part of brick walls;
    • grouting the buried part of concrete walls with cement mortar;
    • jointing of panel walls;
    • whitewashing ceilings;
    • concrete or tiled flooring.
    • The walls of heating points are covered with tiles or painted to a height of 1.5 m from the floor with oil or other waterproof paint, above 1.5 m from the floor - with adhesive or other similar paint.
  • 2.29 At heating points, open pipe laying should be provided. It is allowed to lay pipes in channels, the top of which overlaps with the level of the finished floor, if through these channels no explosive or flammable gases and liquids enter the heating unit.
    • Channels must have removable ceilings with a unit weight of no more than 30 kg.
    • The bottom of the canals must have a longitudinal slope of at least 0.02 towards the drainage pit.
  • 2.30 For servicing equipment and fittings located at a height of 1.5 to 2.5 m from the floor, mobile or portable structures (platforms) must be provided. In cases where it is impossible to create passages for mobile platforms, as well as for servicing equipment and fittings located at a height of 2.5 m or more, it is necessary to provide stationary platforms 0.6 m wide with fences and permanent stairs. The distance from the level of the stationary platform to the ceiling must be at least 1.8 m.
  • 2.31 In the premises of heating points it is allowed to place equipment for drinking water supply and fire-fighting water supply systems of the building, including pumping units, and in the premises of attached and built-in heating points - also equipment for supply ventilation systems serving industrial premises of categories B, D, D for explosion and fire hazards and administrative and service premises.
According to SNiP 03/23/2003 “NOISE PROTECTION”:
  • 11.6 To prevent the penetration of increased noise from engineering equipment into other rooms of the building, you should:
    • ... use floors on an elastic base (floating floors) in ITP;
    • use enclosing structures of rooms with noisy equipment with the required sound insulation.
  • 11.7 Floors on an elastic base (floating floors) should be made over the entire area of ​​the room in the form of a reinforced concrete slab with a thickness of at least 60 - 80 mm. It is recommended to use fiberglass or mineral wool slabs or mats with a density of 50 - 100 kg/m3 as an elastic layer. With a material density of 50 kg/m3, the total load (weight of the slab and unit) should not exceed 10 kPa, with a density of 100 kg/m3 - 20 kPa;
  • 9.13 The floor on the soundproofing layer (gaskets) should not have rigid connections (sound bridges) with the load-bearing part of the floor, walls and other building structures, i.e. must be "floating". A wooden floor or a floating concrete floor base (screed) must be separated along the contour from the walls and other building structures by gaps 1 - 2 cm wide, filled with soundproofing material or product, for example, soft fibreboard, porous polyethylene moldings, etc. P;