Stairs.  Entry group.  Materials.  Doors.  Locks.  Design

Stairs. Entry group. Materials. Doors. Locks. Design

» Transformer substations and distribution devices, their classification and diagrams. Switchgears What are the requirements for switchgears and substations?

Transformer substations and distribution devices, their classification and diagrams. Switchgears What are the requirements for switchgears and substations?

Distribution devices (RU) are electrical installations that serve to receive and distribute electricity and contain switching devices, busbars and connecting busbars, auxiliary devices (compressor, battery, etc.), as well as protection devices, automation and measuring instruments.
There are open devices - outdoor switchgear (all or the main equipment is located in the open air) and closed ones - closed switchgear (equipment is located in the building). Particular attention should be paid to complete switchgears (SGD) as the most common. A complete switchgear is a device consisting of fully or partially closed cabinets or blocks with built-in devices, protection and automation devices and supplied assembled or fully prepared for assembly. Switchgear switchgear is performed both for internal and external outdoor installation.
A substation is an electrical installation used for the conversion and distribution of electricity and consisting of transformers or other energy converters, switchgear, control devices and auxiliary structures. Substations are divided into transformer and converter ones depending on the predominance of one or another function.
Substation where voltage is converted alternating current using a transformer is called transformer (TP). If the alternating current voltage at a transformer transformer is converted to a lower voltage, it is called a step-down, and if it is converted to a higher voltage, it is called a step-up.
A substation fed directly from the energy system (or a factory power plant) is called the main step-down substation (MSS) of the enterprise, and a substation at which electricity is converted into reduced voltage directly to power the electrical receivers of one or more workshops is called a workshop transformer substation (TS).
A point designed to receive and distribute electricity without converting it is called a distribution point (DP), and a distribution point that receives power directly from the energy system (or a factory power plant) is called a central distribution point (CDP).
Transformer and converter substations, as well as distribution devices, are manufactured and supplied complete (KTP, KPP), assembled or fully prepared for assembly.
The source of power supply for most industrial enterprises, as a rule, is energy systems. Only sometimes do enterprises receive energy from their own factory power plants. Electricity supply and energy distribution within the enterprise from its own power plants is carried out mainly at generator voltages of 6 and 10 kV.
Most enterprises are powered from regional substations that are part of the energy system, via high-voltage power lines through step-down transformers installed at consumer substations, through electricity reception and distribution points (GPP, TsRP, RP and TP), as close as possible to consumers.
Transmission and distribution scheme electrical energy shown in Fig. 1. It depends on the distance between the enterprise and the power source (power plant, high-voltage network of the power system), power consumption, territorial location of loads, reliability requirements, category of electrical receivers for uninterruptible power supply, as well as the number of receiving and distribution points at the enterprise.

Rice. 1. Scheme of transmission and distribution of electrical energy:
G1, G2 - generators, RP - distribution point

Page 1 of 12

REQUIREMENTS FOR DISTRIBUTION DEVICES AND TASKS OF THEIR MAINTENANCE

Switchgears(RU) substations are complexes of structures and equipment designed to receive and distribute electrical energy.
Switchgears can be open (OSU) or closed (ZRU). Complete switchgears (KRU) for installation indoors and directly outdoors (KRUN) have become widespread. They are manufactured in stationary and roll-out versions, and are supplied assembled or fully prepared for assembly. Sealed switchgears that use SF6 gas as an insulating and arc-extinguishing medium are called switchgear.

TO The following requirements apply to switchgear equipment::

  1. According to its nominal data, the switchgear equipment must satisfy operating conditions both in normal mode and during short circuit. Under normal operating conditions, heating of conductors by current should not exceed values established by standards. This ensures reliable operation of live parts and guarantees an economically justified service life of the insulation, excluding its accelerated thermal aging. In short circuit mode, the switchgear equipment must have the necessary thermal and electrodynamic resistance.
  2. Equipment insulation must comply rated voltage networks and withstand possible operational voltage increases during switching and atmospheric overvoltages. One of the main conditions for reliable operation of insulating structures is keeping the insulation clean - systematic cleaning, washing, coatings with hydrophobic pastes; for closed switchgear - protection against penetration of dust and harmful gases into the premises; in KRUN - sealing cabinets, coating insulation with hydrophobic pastes.
  3. The equipment must operate reliably under permissible overloads, which should not lead to damage and a reduction in its service life.
  4. Industrial premises Switchgears must be convenient and safe when servicing equipment by personnel. Switchgear switchgears with voltages of 400 kV and higher must be equipped with biological protection means in the form of stationary, portable or inventory screens, and personal protective equipment - shielding suits. Heating of structures located near live parts accessible to personnel should not exceed 50°C.
  5. Temperature and air humidity in the indoor switchgear must be maintained such that dew does not occur on the insulators; temperature in summer time should not exceed 40°C. Ventilation holes must have blinds or metal mesh. Windows in the closed switchgear must be locked or protected with nets, and openings and openings in walls or cells must be sealed to prevent animals from entering. birds. The roof must be in good condition. Floor coverings must not allow the formation of cement dust.
  6. RU must be equipped with working and emergency electric lighting. Lighting equipment must be installed in such a way as to ensure safe operation.
  7. For personnel orientation, all equipment and especially switching device drives must be provided with clear, conspicuous inscriptions indicating the name of the equipment and the dispatcher name of the electrical circuit to which the inscription refers. In the switchgear, an atypical arrangement of the drive handles of bus disconnectors is unacceptable, when, for example, some disconnectors are turned off by moving the drive handle down, others - up. Switches and their drives, disconnectors, separators, short-circuiters and stationary grounding switches must have “On” and “Off” position indicators. Switchgears must be equipped with an interlock that prevents the possibility of erroneous operations with disconnectors, grounding blades, and short circuiters. Locking devices, except mechanical ones, must be permanently sealed.
  8. The RU premises must contain safety equipment and fire extinguishing equipment.

The tasks of maintaining the reactor plant are:

  1. ensuring compliance of operating modes of the reactor plant and individual electrical circuits technical specifications installed equipment;
  2. maintaining at each period of time such a scheme of switchgear and substations so that they best meet the requirements of reliable operation of the power system and trouble-free selective operation of relay protection and automation devices;
  3. systematic supervision and care of equipment and premises of the reactor plant, elimination of the shortest possible time identified malfunctions and defects, since their development may lead to operational failures and accidents;
  4. control over the timely implementation of preventive tests and equipment repairs;
  5. compliance established order and the sequence of switching operations in the switchgear.

Inspection of the reactor plant without shutting down the equipment should be carried out:

  1. at facilities with constant personnel duty - at least once every 3 days, in addition, in the dark to detect the presence of discharges, corona - at least once a month;
  2. at facilities without permanent duty - at least once a month, and at transformer and distribution points - at least once every 6 months.
  3. after switching off the short circuit.

In case of unfavorable weather (heavy fog, sleet, ice) or increased contamination of the outdoor switchgear, additional inspections are required. During inspection, it is strictly prohibited to perform any work on the equipment.
During inspections of the reactor plant, all comments are recorded in a log of defects and malfunctions and brought to the attention of the managers of the energy enterprise, who take appropriate measures to eliminate the identified violations as soon as possible.
RUs with voltages above 1000 V are operated in accordance with the "Rules technical operation electrical stations and networks."
Tests of the electrical equipment of the reactor plant should usually be carried out during periods of its repair.
Routine repairs of the electrical equipment of the reactor plant, as well as checking its operation (testing), must be carried out in accordance with the schedule approved by the chief engineer of the power enterprise, with the exception of unforeseen emergency and other urgent work that is carried out outside the schedule with its own procedure for registering these works.

2.2.1. This chapter applies to switchgear and substations of Consumers with voltages of 0.4 to 220 kV.

2.2.2. The Consumer switchgear room adjacent to premises owned by third parties and containing live equipment must be isolated from them. It must have a separate, lockable exit.

The switchgear equipment, which is in the service of Consumers and used by the energy supplying organization, must be controlled on the basis of instructions agreed upon by the Consumer and the energy supplying organization.

2.2.3. In switchgear rooms, doors and windows must always be closed, and openings in partitions between devices containing oil must be sealed. All holes where the cable passes are sealed. To prevent the entry of animals and birds, all holes and openings in the external walls of the premises are sealed or covered with meshes with a mesh size of (1x1) cm.

2.2.4. Live parts of ballasts and protection devices must be protected from accidental contact. IN special premises(electrical machines, switchboards, control stations, etc.) open installation of devices without protective covers is allowed.

All switchgear (boards, assemblies, etc.) installed outside electrical rooms must have locking devices that prevent non-electrical personnel from accessing them.

2.2.5. Electrical equipment of switchgear systems of all types and voltages must satisfy operating conditions both under normal conditions and during short circuits, overvoltages and overloads.

The insulation class of electrical equipment must correspond to the rated voltage of the network, and surge protection devices must correspond to the insulation level of electrical equipment.

2.2.6. When electrical equipment is located in an area with a polluted atmosphere, measures must be taken to ensure reliable insulation:

In open switchgears (hereinafter referred to as open switchgears) - strengthening, washing, cleaning, coating with hydrophobic pastes;

In closed switchgears (hereinafter referred to as closed switchgears) - protection from the penetration of dust and harmful gases;

In complete outdoor switchgear, cabinets are sealed and insulation is treated with hydrophobic pastes.

2.2.7. Heating by induced current of structures located near live parts through which current flows and accessible to personnel should not exceed 50°C.

2.2.8. The air temperature inside the indoor switchgear in the summer should be no more than 40°C. If it increases, measures must be taken to reduce the temperature of the equipment or cool the air.

Room temperature compressor station must be maintained within (10-35)°C; in the room of gas-insulated switchgear (hereinafter - GIS) - within (1-40)°C.


The temperature of detachable busbar connections in the switchgear must be monitored according to an approved schedule.

2.2.9. Distances from live parts of the outdoor switchgear to trees, tall bush must be such that the possibility of overlap is excluded.

2.2.10. The covering of floors in closed switchgear, switchgear and switchgear switchgear should be such that there is no formation of cement dust.

Premises intended for the installation of cells of a complete gas-insulated switchgear (hereinafter referred to as GIS), as well as for their inspection before installation and repair, must be isolated from the street and other premises. Walls, floors and ceilings must be painted with dust-proof paint.

Cleaning of premises should be done using wet or vacuum methods. The premises must be equipped supply and exhaust ventilation with air suction from below. Air supply ventilation must pass through filters that prevent dust from entering the room.

2.2.11. Cable channels and ground cable trays of outdoor switchgear and closed switchgear must be covered with fireproof slabs, and the places where cables exit from cable channels, trays, from floors and transitions between cable compartments must be sealed with fireproof material.

Tunnels, basements, canals must be kept clean and drainage devices ensure unhindered drainage of water.

Oil receivers, gravel bed, drains and oil outlets must be maintained in good condition.

2.2.12. The oil level in oil switches, instrument transformers and inputs must remain within the oil gauge scale at maximum and minimum temperatures ambient air.

The oil of leaking bushings must be protected from moisture and oxidation.

2.2.13. Roads for vehicle access to the switchgear and substations must be in good condition.

Places where vehicles are allowed to cross cable channels must be marked with a sign.

2.2.14. All keys, buttons and control handles must have inscriptions indicating the operation for which they are intended ("Enable", "Disable", "Decrease", "Add", etc.).

Signal lamps and signaling devices must have inscriptions indicating the nature of the signal ("On", "Off", "Overheating", etc.).

2.2.15. Switches and their drives must have indicators of the off and on positions.

On switches with a built-in drive or with a drive located in close proximity to the switch and not separated from it by a solid opaque fence (wall), it is allowed to install one indicator - on the switch or on the drive. On switches whose external contacts clearly indicate the on position, it is not necessary to have an indicator on the switch and the built-in or non-walled operator.

Drives of disconnectors, grounding knives, separators, short circuiters and other equipment separated from the devices by a wall must have indicators of the off and on positions.

All drives of disconnectors, separators, short circuiters, grounding knives that do not have guards must have devices for locking them in both the on and off positions.

Switchgears equipped with switches with spring drives must be equipped with devices for winding the spring mechanism.

2.2.16. Personnel servicing the reactor plant must have documentation on acceptable operating modes under normal and emergency conditions.

The duty personnel must have a supply of calibrated fuse links. The use of uncalibrated fusible inserts is not permitted. Fuse links must match the type of fuse.

The serviceability of reserve elements of the switchgear (transformers, switches, busbars, etc.) must be regularly checked by switching on voltage within the time limits established by local instructions.

2.2.17. RU equipment must be periodically cleaned of dust and dirt.

The cleaning time is determined by the person responsible for electrical equipment, taking into account local conditions.

Cleaning of switchgear premises and electrical equipment must be carried out by trained personnel in compliance with safety rules.

2.2.18. Locking devices of distribution devices, except mechanical ones, must be permanently sealed. Personnel performing switching operations are not allowed to unlock these devices without authorization.

2.2.19. To apply grounding in switchgear with voltages above 1000 V, as a rule, stationary grounding blades should be used.

The handles of the grounding knife drives should be painted red, and the grounding knife drives, as a rule, should be painted black. Operations with manual drives devices must be manufactured in compliance with safety regulations.

In the absence of stationary grounding blades, places for connecting portable grounding connections to live parts and the grounding device must be prepared and marked.

2.2.20. On the doors and inner walls of closed switchgear chambers, outdoor switchgear equipment, front and internal parts of external and external switchgear indoor installation, assemblies, as well as on the front and back sides of the switchboard panels, inscriptions must be made indicating the purpose of the connections and their dispatch name.

There must be warning posters and signs of the established type on the doors of the switchgear.

On safety panels and (or) connection fuses there must be inscriptions indicating rated current fuse link.

2.2.21. The switchgear must contain electrical protective equipment and personal protective equipment (in accordance with the standards for equipping with protective equipment), fire protection and aids(sand, fire extinguishers) and first aid supplies for accident victims.

For RUs served by operational mobile teams (hereinafter referred to as OVB), protective equipment may be located at the OVB.

2.2.22. Cabinets with equipment for relay protection and automation devices, communications and telemechanics, control cabinets and distribution cabinets of air circuit breakers, as well as drive cabinets oil switches, separators, short circuiters and motor drives of disconnectors installed in switchgear, in which the air temperature may be below the permissible value, must have electric heating devices.

Switching on and off of electric heaters should, as a rule, be carried out automatically. System automatic switching on and shutdown of electric heaters should also provide for constant monitoring of their integrity with the transfer of information to the local control panel and (or) dispatch console.

Oil switches must be equipped with electrical heating devices for the bottoms of tanks and housings, which are switched on when the ambient temperature drops below the permissible level. The temperature values ​​at which electric heaters must be put into operation and decommissioned are established by local instructions, taking into account the instructions of the electrical equipment manufacturers.

2.2.23. Reservoirs of air switches and other devices, as well as air collectors and cylinders must meet the established requirements.

2.2.24. The hinge joints, bearings and rubbing surfaces of the mechanisms of switches, disconnectors, separators, short circuiters and their drives must be lubricated with low-freezing lubricants, and the oil dampers of switches and other devices must be filled with oil, the freezing point of which must be at least 20 ° C below the minimum winter temperature outside air.

2.2.25. Automatic control, protection and alarm devices for the air preparation unit, as well as safety valves must be systematically checked and adjusted in accordance with the manufacturer's instructions.

2.2.26. The time between stopping and subsequent starting of working compressors (non-working pause) must be at least 60 minutes. for compressors with a working pressure of 4.0-4.5 MPa (40-45 kgf/cm2) and at least 90 min. for compressors with a working pressure of 23 MPa (230 kgf/cm2).

Replenishment of air flow by working compressors should be ensured in no more than 30 minutes. for compressors with operating pressure (4.0-4.5) MPa (40-45) kgf/cm2 and 90 min. for compressors with a working pressure of 23 MPa (230 kgf/cm2).

2.2.27. Drying compressed air for switching devices must be carried out thermodynamically.

The required degree of drying of compressed air is ensured when the difference between the nominal compressor and nominal operating pressure of the switching devices is at least two - for devices with a nominal operating pressure of 2 MPa (20 kgf/cm2) and at least four - for devices with a nominal operating pressure (2.6- 4.0) MPa (26-40 kgf/cm2).

2.2.28. Moisture from air collectors with compressor pressure (4.0-4.5) MPa (40-45) kgf/cm2 must be removed at least once every 3 days, and at facilities without permanent duty personnel - according to an approved schedule drawn up on the basis operating experience.

The bottoms of the air collectors and the drain valve must be insulated and equipped with an electric heating device, which is turned on when moisture is removed for the time necessary for the ice to melt when negative temperatures outside air.

Removal of moisture from condensate collectors of groups of cylinders with a pressure of 23 MPa (230 kgf/cm2) must be carried out automatically every time the compressor is started. To avoid freezing of moisture, the lower parts of the cylinders and condensate collectors must be placed in a heat-insulating chamber with an electric heater, with the exception of cylinders installed after the compressed air purification units (hereinafter referred to as the CAP). The BOV water separator must be purged at least 3 times a day.

Checking the degree of drying - the dew point of the air at the outlet of the water treatment plant - should be done once a day. The dew point should be no higher than minus 50°C at positive ambient temperatures and no higher than minus 40°C at negative temperatures.

2.2.29. Internal inspection and hydraulic testing of air collectors and compressor pressure cylinders must be carried out in accordance with established requirements. Internal inspection of tanks of air switches and other devices should be carried out during major repairs.

Hydraulic tests of air circuit breaker tanks must be carried out in cases where inspection reveals defects that cast doubt on the strength of the tanks.

Internal surfaces tanks must have an anti-corrosion coating.

2.2.30. Compressed air used in air switches and drives of other switching devices must be cleaned of mechanical impurities using filters installed in the distribution cabinets of each air switch or on the air duct supplying the drive of each device.

After completing the installation of the air preparation network, before the initial filling of the tanks of air switches and drives of other devices, all air ducts must be purged.

To prevent contamination of compressed air during operation, the following must be purged:

main air ducts at positive ambient temperatures - at least once every 2 months;

air ducts (connections from the network) to the distribution cabinet and from the cabinet to the reservoirs of each pole of switches and drives of other devices with their disconnection from the device - after each major overhaul of the device;

tanks of air circuit breakers - after each major and current repairs, as well as in case of violation of the operating modes of compressor stations.

2.2.31. For air circuit breakers, the ventilation of the internal cavities of the insulators must be periodically checked (for circuit breakers with indicators).

The frequency of inspections should be established based on the recommendations of the manufacturers.

2.2.32. The humidity of SF6 gas in switchgear and gas-insulated circuit breakers must be monitored for the first time no later than a week after filling the equipment with SF6 gas, and then 2 times a year (in winter and summer).

2.2.33. Monitoring of SF6 gas concentration in switchgear and switchgear switchgear rooms should be carried out using special leak detectors at a height of 10 - 15 cm from the floor level.

The concentration of SF6 gas in the room must be within the limits specified in the instructions of the manufacturers of the devices.

Control must be carried out according to a schedule approved by the Consumer’s technical manager.

2.2.34. Leakage of SF6 gas should not exceed 3% of the total mass per year. It is necessary to take measures to fill tanks with SF6 gas when its pressure deviates from the nominal one.

Operations with switches under reduced SF6 gas pressure are not allowed.

2.2.35. Vacuum arc-extinguishing chambers (hereinafter referred to as VAC) must be tested in the volumes and time frames required established by instructions switch manufacturing plants.

When testing KDV with increased voltage with an amplitude value of over 20 kV, it is necessary to use a screen to protect against the resulting X-ray radiation.

2.2.36. Checking the extinguishing chambers of load switches, determining the degree of wear of gas-generating arc extinguishing liners and burning of fixed arc extinguishing contacts is carried out periodically within the time limits established by the person responsible for electrical equipment, depending on the frequency of operation of the load switches.

2.2.37. Draining moisture from the tanks of oil switches must be carried out 2 times a year - in the spring with the onset of positive temperatures and in the fall before the onset of negative temperatures.

2.2.38. Preventive inspections, measurements and tests of reactor plant equipment must be carried out in the scope and within the time limits provided for by the electrical equipment testing standards (Appendix 3).

2.2.39. Inspection of the reactor plant without shutdown should be carried out:

at facilities with permanent staff duty - at least 1 time per 1 day; in the dark to identify discharges, corona - at least 1 time per month;

at facilities without constant personnel duty - at least once a month, and at transformer and distribution points - at least once every 6 months.

In case of unfavorable weather (heavy fog, sleet, ice, etc.) or heavy pollution Additional inspections must be organized at the outdoor switchgear.

All noticed malfunctions must be recorded in the log of defects and malfunctions on the equipment and, in addition, information about them must be reported to the person responsible for electrical equipment.

Noticed malfunctions must be corrected as soon as possible.

2.2.40. During inspection of the reactor plant Special attention the following should be addressed:

condition of the premises, serviceability of doors and windows, absence of leaks in the roof and interfloor ceilings, availability and serviceability of locks;

serviceability of heating and ventilation, lighting and grounding network;

availability of fire extinguishing means;

availability of tested protective equipment;

availability of a first aid kit;

oil level and temperature, no leaks in the devices;

condition of contacts, switches of the low voltage switchboard;

integrity of seals on meters:

insulation condition (dustiness, presence of cracks, discharges, etc.);

absence of damage and traces of corrosion, vibration and crackling in SF6 equipment;

operation of the alarm system;

air pressure in tanks of air circuit breakers;

compressed air pressure in the reservoirs of pneumatic drives of switches;

no air leaks;

serviceability and correctness of indications of switch position indicators;

the presence of ventilation of the poles of air circuit breakers;

no oil leakage from capacitors of capacitive voltage dividers of air circuit breakers;

operation of electric heating devices in the cold season;

closure density of control cabinets;

possibility of easy access to switching devices, etc.

2.2.41. Major repairs of reactor plant equipment must be carried out within the following time limits:

oil switches - once every 6 - 8 years when monitoring the characteristics of the switch with a drive during the overhaul period;

load switches, disconnectors and grounding blades - once every 4 - 8 years (depending on design features);

air switches - once every 4-6 years;

separators and short-circuiters with an open knife and their drives - 1 time every 2 - 3 years;

compressors - once every 2-3 years;

GIS - once every 10-12 years;

SF6 and vacuum circuit breakers - once every 10 years;

conductors once - every 8 years;

of all devices and compressors - after exhaustion of their service life, regardless of the duration of operation.

First major renovation installed equipment must be carried out within the time limits specified in technical documentation manufacturer.

Indoor disconnect switches should be repaired as needed.

Repair of reactor plant equipment is also carried out as necessary, taking into account the results of preventive tests and inspections.

The frequency of repairs can be changed, based on operating experience, by the decision of the technical manager of the Consumer.

Extraordinary repairs are carried out in the event of equipment failures, as well as after the switching or mechanical resource has been exhausted.

Switchgear (RU) is an electrical installation designed to receive and distribute electrical energy, containing electrical devices, buses and auxiliary devices. Electrical stations, step-down and step-up substations, usually have several switchgears of different voltages (HV switchgear, LV switchgear, LV switchgear).

Essentially RU - this is a constructive implementation of accepted electrical diagram substations, i.e. arrangement of electrical devices indoors or outdoors with connections between them with bare (rarely insulated) busbars or wires strictly in accordance with the electrical diagram.

For the energy system, the reactor plant is a network node equipped with electrical devices and protective devices, serving to control the distribution of energy flows, disconnect damaged areas, and ensure reliable power supply to consumers.

Each switchgear consists of suitable and outgoing connections, which are interconnected by busbars, jumpers, ring and polygonal connections, with the placement of a different number of switches, disconnectors, reactors, instrument transformers and other electrical devices determined by the adopted circuit. All similar connections are made in the same way, so the switchgear is assembled from standard, seemingly standard, cells.

RU must meet certain requirements, the most important of them are: reliability of operation, convenience and safety of maintenance when minimum costs on construction, fire safety and economical operation, possibility of expansion, maximum application large-block prefabricated units.

Reliability of switchgear operation is ensured the right choice And correct installation electrical equipment (electrical devices, live parts and insulators), as well as good localization of accidents with electrical equipment if they occur. In addition, the reliability of the reactor plant largely depends on the quality of construction and electrical installation work.

RU are performed for all applicable voltages. By analogy with the devices, they are divided into switchgear up to 1000 kV, high voltage switchgear from 3 to 220 kV, ultra-high voltage switchgear: 330, 500, 750 kV and promising ultra-high voltage switchgear 1150 kV and higher.

According to their design, switchgears are divided into closed (internal), in which all electrical equipment is located inside the building, and open (external), in which all electrical equipment is located in the open air.

Rice. 2.1. GRU 6 – 10 kV with one bus system and group reactors (section along the generator and group reactor circuits) 1 - current transformer, 2 - bushing insulator, 3 - generator circuit breaker chamber, 4 - circuit breaker drive, 5 - busbar block, 6 - busbar disconnector block, 7 - busbar disconnector drive, 8 - double reactor chamber, 9 - busbar duct, 10 – switchgear cells

Closed switchgear (SGD) - This is a distribution device located inside the building. They are usually built at a voltage of 3 – 20 kV. In high voltage installations, 35 - 220 kV, closed switchgears are built only with a limited area under the switchgear, when they are located in close proximity to industrial enterprises that pollute the air with conductive dust or gases that destroy insulation and metal parts of electrical equipment, as well as near sea ​​coasts and in areas with very low air temperatures (regions of the Far North).

Maintenance of indoor switchgear should be convenient and safe. For safety, the minimum permissible distances from live parts to various elements ZRU

To avoid accidental touching, uninsulated live parts must be placed in chambers or fenced. The fence can be solid or mesh. In many indoor switchgears, mixed fencing is used - the drives of switches and disconnectors are mounted on the solid part of the fencing, and the mesh part of the fencing allows observation of the equipment. The height of such a fence must be at least 1.9 m, while the mesh must have holes measuring no more than 25x25 mm, and the fences must be locked.

From the indoor switchgear rooms, exits are provided to the outside or to rooms with fireproof walls and ceilings: one exit for a switchgear length of up to 7 m; two exits at the ends with a length of 7÷60 m; for a length of more than 60 m - two exits at the ends and additional exits so that the distance from any point in the corridor to the exit does not exceed 30 m. The switchgear doors must open outward, have self-locking locks and open without a key from the switchgear side.

ZRU must provide fire safety. When installing oil transformers in closed switchgear, measures are taken to collect and drain oil into the oil collection system. The ZRU provides natural ventilation rooms of transformers and reactors, as well as emergency exhaust of service corridors open cells with oil-filled equipment.

Prefabricated switchgear (SRU) assembled from enlarged units (cabinets, panels, etc.), manufactured and equipped in factories or workshops. In the SBRU the building is constructed in the form of a box, without any partitions, of a hall type. The basis of the chambers is a steel frame, and the partitions between the chambers are made of asbestos-cement or gypsum boards.

Rice. 2.2. 110 kV indoor switchgear (section through an air circuit breaker cell)1 - VNV-110 kV circuit breaker, 2 - first busbar system, 3 - busbar disconnectors, 4 - second busbar system, 5 - bypass busbar system, 6 - bypass disconnector, 7 - coupling capacitor, 8 - line disconnector.

Complete switchgear (KRU) - this is a switchgear completely manufactured in factories, consisting of closed cabinets with built-in devices, measuring and protective instruments and auxiliary devices; All switchgear elements are only mounted on site. These switchgears best meet the requirements of the industrialization of energy construction, so they are currently becoming the most common form of switchgear design. The use of switchgear allows you to speed up the installation of the switchgear. The switchgear is safe to maintain, since all live parts are covered with a metal casing. Air, oil, pyralene, solid insulation, and inert gases can be used as insulation between live parts in switchgear. Switchgear with oil and gas insulation can be manufactured at high voltage 220 – 500 kV. Our industry produces switchgear of 3 - 35 kV with air insulation and 110 - 220 kV with SF6 insulation (in world practice up to 800 kV). Complete outdoor switchgears (KRUN) are designed for open installation outside

premises. KRUN consist of metal cabinets with built-in devices, instruments, protection and control devices. KRUN are designed to operate at ambient temperatures from -40 to +35 ° C and air humidity of no more than 80%. KRUN can have a stationary installation of a circuit breaker in a cabinet or a roll-out trolley with a circuit breaker, similar to an indoor switchgear installation.

Cabinets KRZ-10 (Fig. 2.3) for outdoor installation 6 – 10 kV are intended for networks Agriculture, industry and electrification of railway transport. KRZ-10 cabinets are designed for temperatures environment from +50 to -45°С.

At the same time, at present, mixed-type switchgears are also widely constructed, partly as prefabricated and partly as complete ones.

Rice. 2. 4. Typical layout of outdoor switchgear 110 - 220 kV for a circuit with two working and bypass bus systems

1 – bypass SB, 2 – SBH disconnector, 3 – coupling capacitor, 4 – arrester, 5 – linear disconnector, 6 – current transformer, 7 – air circuit breaker, 8 – second SB, 9 – keel-type bus disconnectors, 10 – bus disconnectors , 11 – first secondary school.

Open switchgear (OSD)- This is a distribution device located in the open air. As a rule, switchgear switchgears in electrical installations with voltages of 35 and above are constructed open. The simplest open substations of low power with a primary voltage of 10(6)-35 kV are also widespread for the electrification of agricultural and suburban areas, industrial villages and small towns.

All devices in outdoor switchgear are installed on low foundations (metal or reinforced concrete). Passages are made through the territory of the outdoor switchgear to enable mechanization of installation and repair of equipment. Busbars can be flexible stranded wires or rigid pipes. Flexible busbars are secured using suspension insulators on portals, and rigid busbars are secured using support insulators on reinforced concrete or metal racks.

The use of rigid busbars makes it possible to abandon portals and reduce the area of ​​outdoor switchgear.

An oil receiver is provided under power transformers, oil reactors and tank switches of 110 kV and above, a layer of gravel at least 25 cm thick is laid, and the oil flows in emergency cases into underground oil collectors. Cables of operational circuits, control circuits, relay protection, automation and air ducts are laid in trays made of reinforced concrete structures without burying them in the soil or in metal trays suspended from outdoor switchgear structures.

The outdoor switchgear must be fenced.

Advantages of outdoor switchgear compared to indoor switchgear

1) smaller volume construction work; since only site preparation, road construction, foundation construction and installation of supports are necessary;

2) significant savings building materials(steel, concrete);

3) smaller capital expenditures;

4) shorter construction time;

5) good visibility;

6) ease of expansion and ease of replacing equipment with others with smaller or larger dimensions, as well as the ability to quickly dismantle old and install new equipment.

7) less risk of damage spreading due to long distances between devices of adjacent circuits;

Disadvantages of outdoor switchgear compared to indoor switchgear

1) less convenient maintenance, since switching disconnectors and monitoring devices is carried out in the air in any weather (low temperatures, bad weather);

2) big square structures;

3) exposure of devices to sudden changes in ambient temperature, their vulnerability to pollution, dust, etc., which complicates their operation and forces the use of devices of a special design (for outdoor installation), which are more expensive.

The cost of indoor switchgear is usually 10–25% higher than the cost of the corresponding outdoor switchgear.

Currently, in most cases, outdoor switchgear is used of the so-called low type, in which all devices are located in the same horizontal plane and installed on special bases of a relatively small height; prefabricated busbars are mounted on supports that are also of relatively low height.

4.1.24. Switchgears installed in rooms accessible to uninstructed personnel must have live parts covered with solid fences.

If a switchgear is used with open live parts, it must be fenced. In this case, the fence must be mesh, solid or mixed, with a height of at least 1.7 m. The distance from the mesh fence to the non-insulated live parts of the device must be at least 0.7 m, and from solid ones - in accordance with 4.1.14. The width of passages is taken in accordance with the requirements given in 4.1.21.

4.1.25. The termination of wires and cables must be made so that it is located inside the device.

4.1.26. Removable barriers must be strengthened so that their removal is impossible without the use of tools. The doors must be locked with a key.

4.1.27. The installation of complete switchgears and substations (switchgear switchgear, package transformer substations) must comply with the requirements given in Chapter. 4.2 for switchgear and package substations above 1 kV.

Installation of switchgear outdoors

4.1.28. When installing switchgear outdoors, the following requirements must be observed:

1. The device must be located on a planned site at a height of at least 0.2 m from the planning level and must be designed in accordance with environmental conditions. In areas where snow drifts of 1 m or more in height are observed, cabinets should be installed on elevated foundations.

2. Local heating must be provided in the cabinets to ensure normal operation of devices, relays, measuring instruments and metering devices in accordance with GOST requirements.

Chapter 4.2

Switchgears and substations

Voltage above 1 kV

Scope, definitions

4.2.1. This chapter of the Rules applies to stationary switchgear and alternating current substations with voltages above 1 kV. The rules do not apply to special switchgear and substations regulated by special technical specifications, and for mobile electrical installations.

4.2.2. A switchgear is an electrical installation that serves to receive and distribute electricity and contains switching devices, busbars and connecting busbars, auxiliary devices (compressor, battery, etc.), as well as protection devices, automation and measuring instruments.

An open switchgear (OSD) is a switchgear, all or the main equipment of which is located in the open air.

A closed switchgear is called a switchgear, the equipment of which is located in the building.

4.2.3. A complete switchgear is a switchgear consisting of fully or partially closed cabinets or blocks with built-in devices, protection and automation devices, supplied assembled or fully prepared for assembly.

A complete switchgear intended for indoor installation is abbreviated as KRU. A complete switchgear intended for outdoor installation is abbreviated as KRUN.

4.2.4. A substation is an electrical installation used for the conversion and distribution of electricity and consisting of transformers or other energy converters, switchgear, control devices and auxiliary structures.

Depending on the predominance of one or another function of substations, they are called transformer or converter.

4.2.5. An attached substation (attached RU) is a substation (RU) directly adjacent (adjacent) to the main building.

4.2.6. A built-in substation (built-in switchgear) is a closed substation (closed switchgear), inscribed (inscribed) in the contour of the main building.

4.2.7. An intra-shop substation is a substation located inside a production building (open or in a separate enclosed room).

4.2.8. A complete transformer (converter) substation is a substation consisting of transformers (converters) and units (switchgear or switchgear and other elements) supplied assembled or fully prepared for assembly. Complete transformer (converter) substations (KTP, KPP) or parts of them installed indoors are classified as indoor installations; those installed outdoors are classified as outdoor installations.

4.2.9. A pole (mast) transformer substation is an open transformer substation, all of whose equipment is installed on structures or on overhead line supports at a height that does not require substation fencing.

4.2.10. A distribution point (DP) is a switchgear intended for receiving and distributing electricity at one voltage without conversion and transformation, which is not part of the substation.

4.2.11. A chamber is a room intended for the installation of devices and tires.

A closed cell is a cell that is closed on all sides and has solid (not mesh) doors.

A fenced chamber is a chamber that has openings protected in whole or in part by non-solid (mesh or mixed) fences.

Mixed fencing refers to fencing made from mesh and solid sheets.

An explosion chamber is a closed chamber designed to localize possible emergency consequences of damage to the devices installed in it and having access to the outside or into the blast corridor.

4.2.12. A service corridor is a corridor along the switchgear chambers or cabinets, intended for servicing devices and buses.

An explosive corridor is a corridor into which the doors of the explosive chambers open.